Medium-voltage switchgear in Colombia: what it is and how to specify it

Learn when to use switching, metering and protection panels. Compare air and gas insulation, review Colombia’s RETIE and explore AMAR projects in Cartagena and Guasca.

AMAR Colombia ·

Medium-voltage switchgear from the AMAR Colombia catalogue
Illustration from the AMAR Colombia catalogue.

What is medium-voltage switchgear?

A medium-voltage panel is an assembly of electrical equipment installed in an enclosure. Depending on its configuration, it switches a circuit, houses metering equipment or protects a feeder or transformer. A customer substation may use several panels between the incoming supply and the transformer. Panels also serve internal distribution downstream of the utility connection point.

A typical path is utility network → incoming supply → switchgear lineup → transformer → low-voltage switchboard. The project single-line diagram defines the required functions, their order and the commercial metering boundary.

Switching, metering and protection

Functions a switchgear lineup may provide
FunctionWhat it doesWhat to check
SwitchingConnects, disconnects or isolates sections according to the installed device.Load-switching capability, interlocks and earthing.
MeteringHouses current and voltage transformers where the scheme requires them.Ratios, accuracy classes and commercial metering requirements.
ProtectionClears faults through a relay-operated circuit breaker or a switch-fuse combination where the design allows it.Interrupting rating and coordination with upstream and downstream protection.

A disconnector, a load-break switch and a circuit breaker have different capabilities. For revenue metering, confirm the scheme with the network operator and consult CREG’s Metering Code.

Connection voltages in Colombia

Enel Colombia documents 11.4 kV, 13.2 kV and 34.5 kV networks. In Antioquia, EPM documents 13.2 kV and 44 kV networks in its eastern Antioquia project. These are examples of specific networks. Use the connection conditions issued by the operator for the site as the design basis.

Air-insulated, SF₆ and SF₆-free switchgear

  • Air-insulated switchgear (AIS). Review installation footprint, cable entry, room conditions and access and maintenance options.
  • Gas-insulated switchgear (GIS). A sealed vessel can help protect the components it houses and enable compact designs. Review the conditions outside the vessel, cable terminations and the exact model’s ratings.
  • SF₆-free options. Compare available voltage and ratings, dimensions, local support and end-of-life handling. Specify the insulation and interruption media separately.

As a manufacturer example, Siemens documents the 8DJH 36 series for secondary distribution up to 36 kV, with a sealed stainless-steel vessel and SF₆ insulation. Siemens also documents the NXPLUS C 24 – blue GIS series up to 24 kV. Compare the exact quoted configuration and its tests. In oil and gas, if the location is classified for an explosive atmosphere, the design must verify suitability for that location.

What to check under RETIE and IEC 62271-200

Book 2 of RETIE, section 2.3.31.4 of Resolution 40117 of 2024, sets product and test requirements for medium-voltage switchgear. It addresses internal arc effects, interlocks, earthing and dielectric tests. Consult the Ministry’s portal for applicable amendments and transition provisions, including Resolution 40304 of 2025.

IEC 62271-200 covers AC metal-enclosed assemblies rated above 1 kV through 52 kV. Where the project calls for an IAC internal arc classification, verify accessibility, covered sides, current and duration. Check the installation against the tested conditions, including room clearances and exhaust paths. Where continuity during compartment access matters, review the applicable LSC category.

Request evidence that matches the quoted assembly, model, configuration and ratings. RETIE treats complete assembly certification separately from enclosure certification. The project must also verify the applicable installation design, construction and inspection requirements.

What service continuity means for the project

Superservicios reported that municipalities in its urgent or higher criticality categories fell from 89 in 2024 to 64 in 2025 under its individual service quality monitoring methodology. El Espectador highlighted persistent critical issues in the Caribbean region. In Urabá, El Colombiano reported on the connection between Puerto Antioquia and EPM’s Nueva Colonia substation, illustrating how permits, land availability and connection work can affect a project schedule.

For a clinic, public facility or industrial plant, plan continuity around site-level interruption history and the loads that must remain online. Switchgear enables fault isolation and switching according to the design. Backup systems such as UPS units, generators or an alternative supply provide autonomy, together with the appropriate transfer equipment.

AMAR projects in Cartagena and Guasca

Cartagena renal clinic and project electrical equipment
Cartagena, Bolívar · 2019

Cartagena renal clinic

AMAR supplied and installed a 300 kVA substation, low-voltage switchboards, medium-voltage switchgear and a transformer.

Guasca police station and its project electrical cabinets
Guasca, Cundinamarca · 2022

Guasca police station

AMAR supplied medium-voltage switchgear and a transfer switch for the station.

The scopes illustrate two different contracts: an installed substation for a clinic and equipment supply for a public facility. AMAR’s project portfolio documents both scopes.

What to send for a switchgear specification or quotation

  1. Connection: municipality, network operator, approved conditions, service voltage and metering scheme.
  2. Design: single-line diagram, transformer rating, required continuous current, insulation level and fault study at the installation point.
  3. Protection: device type, interrupting and short-time withstand ratings, coordination study and signals required for remote monitoring.
  4. Installation: altitude, temperature, humidity, pollution or salt exposure, room dimensions, access, cable entry and arc exhaust provisions.
  5. Delivery: applicable RETIE documentation, test evidence, drawings, supply scope and requirements for acceptance testing and commissioning.

For example, a 300 kVA three-phase transformer connected at 13.2 kV has a nominal primary current of about 13.1 A (300 kVA ÷ [√3 × 13.2 kV]). This illustrative calculation describes the transformer’s nominal load. Protection selection also depends on fault current, transformer energization and utility coordination.

Frequently asked questions

What is the difference between metering and protection panels?

A metering panel houses equipment that feeds the metering system. A protection panel contains the device that clears faults within its rating and according to the coordination scheme.

What voltage rating should my switchgear have?

Start with the voltage and connection conditions issued by the network operator. Then verify equipment class, insulation level, fault duty and the manufacturing standard required for the project.

When should I consider GIS?

Consider GIS when the footprint, environment or substation configuration favours a compact design or sealed vessel. Compare the exact model, site conditions and local support.

What does IAC mean on a switchgear datasheet?

IAC identifies an internal arc classification. Read it with the accessibility, covered sides, test current and duration, and mounting conditions for the model.

Does switchgear maintain power during an outage?

Switchgear can switch circuits and isolate faults according to the design. Loads requiring autonomy depend on a backup supply and the project’s transfer and distribution architecture.

Sources and references

AMAR products for this topic

Medium voltage switchgear

Medium voltage switchgear

Switching and protection for your substation, in SF6 and air — the SF6 ones are Siemens. All of them factory-assembled and type-tested.

Low voltage switchboards

Low voltage switchboards

We select them against your single-line diagram, certified and type-tested to IEC 61439-1. They arrive ready to install, with the delivery date committed in writing.